TD Mixvent 6000/400
Code: SP200100120Related products
Product detailed description
The TD-6000 housing is made of galvanised steel sheet with an epoxy coating. The housing consists of a mounting rail with two spigots and a motor connected to the spigots by quick-release clamps. The design allows the motor section to be removed without disconnecting the ducting.
The TD-4000 and TD-6000 motors have a single winding and can be regulated by changing the voltage. The motor is equipped with thermal protection.
TD 4000 and 6000 can only be regulated by changing the voltage.
The terminal block is located on the fan housing, and on some types it contains a starting capacitor.
Fan installation is possible in any fan position. The housing must not transfer mechanical stress from the ductwork. A flexible connection to the ducting is required.
Parameters:
- air flow: 5310/4860/4440/3580 m3/h
- speed: 1400/1320/1210/960 rpm
- duct diameter: 400 mm
- power: 680/577/530/453 W
- voltage: 230/170/140/115 V
- current: 2.92/3.24/3.66/4.06 A
- noise level: 44 db(A)
- protection rating: IP54
- max. temperature: -40 to +40 °C
Operating instructions here: TD instructions
Product information catalogue: TD catalogue
Dimensions (in mm):
*the fan drawing can be found in the photo gallery
Additional parameters
| Category: | TD Mixvent Fans |
|---|---|
| EAN: | HSP200100120 |
| Flange (mm): | 400 |
| Speed Control: | No regulation |
| Technology: | Axial |
| Airflow (m3/h): | 6000 |
| PFHGX: | Levné, Best-selling, Doporučené, High-quality, Značkové, Základní |